Page 47 - Op_K_2025_absolute Links
P. 47

OPP-SENS® Duct absolute

               humidity temperature sensors
                                                                            Type              Item no. ADG Euro  /  pc.

                             OPP-SENS® Duct humidity temperature sensor     HTa-xxx-I-...       see       see
                             (absolute humidity)                                              following   following
                             for measurement of absolute humidity and temperature              page       page
                             in ventilation ducts.
                             Display and control unit with autoadapt and capacitive
                             button (option). This enables the NFC function, allowing easy
                             sensor parameterization via a smartphone.
                             5-point calibration: linear interpolation of the output curve
                             over 5 user-defined points.                                                              SENSORS
                             10 offset points: linear shift of characteristic curve the output
                             signal via 10-level rotary switch.
                             Captive lid with 8-way positioning.

                             10 measurement ranges can be set using the rotary switch:
                             0 – 15 g / m³   0 – 20 g / m³   0 – 35 g / m³   0 – 50 g / m³*
                             0 – 100 g / m³  0 – 130 g / m³  0 – 150 g / m³  0 – 200 g / m³
                             0 – 300 g / m³  0 – 500 g / m³  *factory settings
                             Measuring range
                             temperature:            Factory settings -50 to 50 °C,
                                                   with adjustable optional display
                                                   between -50 and 100 °C
                             Supply voltage:
                             2-wire                24 V DC
                             3-wire / Modbus / BACnet   24 V AC / DC
                             Output:
                             2-wire                4 – 20 mA
                             3-wire                0 – 10 V or 4 – 20 mA
                                                   switchable or bus
                             Margins of error:
                             Humidity              ± 3 % RH at 25 °C for 20 – 80 % RH
                             Temperature           ± 0.5 °C for 0 – 65 °C
                             Permiss.
                             ambient conditions:     -20 – 70 °C, 0 – 95 % RH
                                                   (non-condensing)
                             Permiss. media temp.:    -40 – 100 °C
                             Nominal diameter:     Stainless steel sleeve ø 10 mm
                             Mounting:             air duct mounting flange F-10
                                                   (included)
                             Housing:              IP 65 including seal,
                                                   Plastic gray / yellow
                             Terminals:            Spring terminals 0.2 – 1.5 mm2
                             Cable gland:          M16

























               To our online catalog: www.oprg.de/en/support/download-center              Catalog 2025  |  Sensors  |  47