Page 45 - Op_K_2025_absolute Links
P. 45

OPP-SENS® Duct relative

               humidity temperature sensors
                                                                            Type              Item no. ADG Euro  /  pc.

                             OPP-SENS® Duct humidity temperature sensor     HT-xxx-I-...        see       see
                             (relative humidity)                                              following   following
                             for measurement of relative humidity and temperature              page       page
                             in ventilation ducts.
                             Display and control unit with autoadapt and capacitive
                             button (option). This enables the NFC function, allowing easy
                             sensor parameterization via a smartphone.
                             5-point calibration: linear interpolation of the output curve over
                             5 user-defined points.                                                                   SENSORS
                             10 offset points: linear shift of characteristic curve the output
                             signal via 10-level rotary switch.
                             Captive lid with 8-way positioning.
                             Output 1 humidity:    0 – 100 % RH linear
                             Output 2 temperature:    -50 – 50 °C linear
                             Supply voltage:
                             2-wire                24 V DC
                             3-wire / Modbus / BACnet   24 V AC / DC
                             Output:
                             2-wire                4 – 20 mA
                             3-wire                0 – 10 V or 4 – 20 mA
                                                   switchable or bus
                             Margins of error:
                             Humidity              ± 3 % RH at 25 °C
                                                   for 20 – 80 % RH
                             Temperature           ± 0.5 °C for 0 – 65 °C
                             Permiss.
                             ambient conditions:     -20 – 70 °C, 0 – 95 % RH
                                                   (non-condensing)
                             Permiss. media temp.:   -40 – 100 °C
                             Nominal diameter:     Stainless steel sleeve ø 10 mm
                             Mounting:             air duct mounting flange F-10
                                                   (included)
                             Housing:              IP 65 including seal,
                                                   Plastic gray / yellow
                             Terminals:            Spring terminals 0.2 – 1.5 mm2
                             Cable gland:          M16


































               To our online catalog: www.oprg.de/en/support/download-center              Catalog 2025  |  Sensors  |  45
   40   41   42   43   44   45   46   47   48   49   50