Page 49 - Op_K_2025_absolute Links
P. 49

OPP-SENS® Duct enthalpy

               humidity temperature sensors
                                                                            Type              Item no. ADG Euro  /  pc.

                             OPP-SENS®Duct humidity temperature sensor (enthalpy)  HTx-xxx-I-...  see     see
                             For measuring enthalpy temperature in air ducts.                 following   following
                             The optional display enables you to configure the transmitter such   page    page
                             that it indicates and outputs absolute or relative humidity or the
                             mixture ratio instead of enthalpy. The absolute air pressure can also
                             be set via the display.
                             Display and control unit with autoadapt and capacitive
                             button (option). This enables the NFC function, allowing easy
                             sensor parameterization via a smartphone.                                                SENSORS
                             5-point calibration: linear interpolation of the output
                             curve over 5 user-defined points.
                             10 offset points: linear shift of characteristic curve the output
                             signal via 10-level rotary switch.
                             Captive lid with 8-way positioning.

                             10 measurement ranges can be set using the rotary switch:
                             0 – 50 kJ / kg   0 – 80 kJ / kg   0 – 100 kJ / kg*  0 – 200 kJ / kg
                             0 – 400 kJ / kg   0 – 1000 kJ / kg   -50 – 50 kJ / kg   -50 – 200 kJ / kg
                             -50 – 400 kJ / kg  -50 – 1000 kJ / kg  *factory settings
                             Measuring range
                             temperature:            Factory settings -50 to 50 °C,
                                                   with adjustable optional display
                                                   between -50 and 100 °C
                             Supply voltage:
                             2-wire                24 V DC
                             3-wire / Modbus / BACnet   24 V AC / DC
                             Output:
                             2-wire                4 – 20 mA
                             3-wire                0 – 10 V or 4 – 20 mA
                                                   switchable or bus
                             Margins of error:
                             Humidity              ± 3 % RH at 25 °C for 20 – 80 % RH
                             Temperature           ± 0.5 °C for 0 – 65 °C
                             Permiss.
                             ambient conditions:     -20 – 70 °C, 0 – 95 % RH
                                                   (non-condensing)
                             Permiss. media temp.:    -40 – 100 °C
                             Nominal diameter:     Stainless steel sleeve ø 10 mm
                             Mounting:             air duct mounting flange F-10
                                                   (included)
                             Housing:              IP 65 including seal,
                                                   Plastic gray / yellow
                             Terminals:            Spring terminals 0.2 – 1.5 mm2
                             Cable gland:          M16






















               To our online catalog: www.oprg.de/en/support/download-center              Catalog 2025  |  Sensors  |  49
   44   45   46   47   48   49   50   51   52   53   54