OPP-SENS® Differential air pressure

          volume flow transmitter
                                                                      Type              Item no. ADG Euro  /  pc.

                       OPP-SENS® Differential air pressure            PV…                 See        See
                       volume flow transmitter                                          following   following
                       for measuring pressure differential and volume flow of            page       page
                       non-combustible and non-aggressive gases and air.
                       With manual zero point setting.
                       Selectively configurable from 0 – 1,000 Pa and 0 – 4,000 Pa,
                       depending on desired accuracy.
                       Adjustable linear or square root extraction output of pressure
                       differential on analog transmitters (factory setting: linear).
                       The data is always transmitted in the form of registers in the
                       bus version.
                       Volume flow is calculated by entering correction factor k or
                       selecting a fan manufacturer and is output as a linear output
                       signal or via bus.
                       Volume flow measurement range: 0 – 99,000 m³ / h.
                       Display and control unit with autoadapt and capacitive
                       button (option). This enables the NFC function, allowing easy
                       sensor parameterization via a smartphone.
                       5-point calibration: linear interpolation of the output
                       curve over 5 user-defined points.
                       10 offset points: linear shift of characteristic curve
                       the output signal via 10-level rotary switch.
                       Captive lid with 8-way positioning.
                       Optional integration of fan walls/fan grids.
                       10 pressure sensor ranges selectable with rotating switch:

                       Version AD1 (0 – 1,000 Pa):
                       0 – 100   0 – 200    0 – 300   0 – 400
                       0 – 500   0 – 600    0 – 700   0 – 800
                       0 – 900   0 – 1,000 Pa* *factory setting

                       Version AD4 (0 – 4,000 Pa):
                       0 – 400   0 – 800    0 – 1,200   0 – 1,600
                       0 – 2,000   0 – 2,400   0 – 2,800   0 – 3,200
                       0 – 3,600   0 – 4,000 Pa* *factory setting

                       Power supply:
                       2-wire              24 V DC
                       3-wire / Modbus / BACnet   24 V AC / DC
                       Outputs:
                       2-wire              4 – 20 mA
                       3-wire              0 – 10 V or 4 – 20 mA
                                           switchable or bus
                       Burst pressure AD1:   15 kPa
                       Burst pressure AD4:   40 kPa
                       Permiss. amb. cond.:      -20 – 70 °C, 0 – 95 % RH
                                           (non-condensing)

                       Permiss.
                       media temperature:    -5 – 65 °C
                       Error Margin:         ±1 % of sensor range limit value
                                           at -5 – 65 °C
                       Housing:            IP 65 including seal
                                           Plastic gray / yellow
                       Cable gland:        M16
                       Terminals:          Spring terminals 0.2 – 1.5 mm2