Page 108 - Op_K_2025_absolute Links
P. 108

OPP-SOR® CO warning devices

          for car parks and tunnels (bus technology)



          System description for TGÜ-BM 3.6
          The TGÜ-BM 3.6 is a bus-capable measurement and control   the sensor electronics. The measured data are corrected for
          system for monitoring air quality in underground garages and   temperature, rescaled and evaluated based on the set averaging
          other enclosed spaces in which combustion engine vehicles are   time. Exceedances of set threshold values trigger control commands
          operated for toxic concentrations of carbon monoxide,    via relay to blowers, warning signs, horns, device malfunction alarms
          nitric oxides or propane.                        (GMS) and the building management system (GLT).
          The TGÜ-BM 3.6 allows different types of gas sensors to be used   A total of 4 variable threshold values can be set independently
          simultaneously and can manage up to 240 sensors. Four alarm   of each other based on averaging time and hysteresis.
          zones with up to 60 sensors each are integrated into the central   Alarm thresholds can be tested by alarm simulation using
          control unit. If larger numbers are required, it is necessary to add   an inbuilt virtual sensor.
          a further central control unit.                  The TGÜ-BM 3.6 can be parameterized via an interactive web
          The sensors are connected to the TGÜ-BM 3.6 by 4 lines: 2 for the   interface. For this purpose the device needs to be connected to an
          power supply and 2 for data transfer. Communication between   TCP / IP network via the integrated Ethernet interface. Access to the
          the central control unit and the gas sensors is performed   web interface is password-protected to prevent misuse.
          digitally via a bus system. The control unit samples the gas   The connection to the building management system can be
          sensors cyclically and stores the instantaneous values for further   established via Modbus.
          processing. In this way the bus and sensors are also monitored   Gas sensor calibration is performed locally for each gas sensor using   GLT
          themselves, and any malfunction is detected and reported.   a hand-held device. The supply voltage is 230 V AC, and connection
          The measurement signal of the gas sensors is digitalized in   to an uninterruptible power supply (24 V DC) is required.
                                                                                                                                  monitoring/data logging
                                                                      Typ               Item no. ADG Euro / pc.
                       OPP-SOR® Monitoring device for underground car parks  TGÜ-BM 3.6  104424  33  2,103.20                           Ethernet/LAN
                       for up to 240 OPP-SOR® gas sensors as stated in the system                                                       power supply
                       description. Supply voltage 230 V AC / 50 – 60 Hz or 24 V DC.                                                       230 V AC
                       4 alarm zones integrated. Max. 60 gas sensors per zone. 4 Alarm     zone 1  zone 2   zone 3   zone 4                 24 V DC
                       switching points with average or actual value setting.
                       1 collective failure output with floating change-over contacts.   GMF gas sensor  ...  ...     ...
                       7 switching relay outputs for ventilators 1 + 2 + 3, signal horn,          BMS
                       warning sign, device malfunction and BMS. 4 digital control inputs.        relay
                       TFT color LCD display with language selection for operating, alarm         fault                                integrated
                       und error messages as well as for indication of sampling point             relay                                time switch
                       information such as gas type and concentration value. 8-key
                       operation on device.
                       Calculation of averages, system clock for data recording
                       functionality, self-monitoring, bus monitoring, data interface              LED warning sign
                       RS485, Modbus. Ethernet interface for connection to TCP/ IP-based
                       networks. Modbus interface for connection to the BMS. Plastic
                       on-wall housing with cover.
                                                                                                    horn
                       Protection class:    IP 54                                    option
                       Dimensions:      340 x 230 x 112 mm (W x H x T)                                blower  1
                       Strain relief:     17x M16, 2x M20 and an M20 divisible
                                        screw connection                                              blower  2
                       Integrated time switch for cyclic ventilation & optional humidity
                                                                       outdoor
                                                                                  indoor
                       monitoring. This makes it possible to monitor underground   humidity  humidity  blower  3
                       garages with even greater energy efficiency and additionally   Option
                       activate cyclic ventilation as required. The optional humidity
                       monitoring function prevents additional moisture from entering
                       the garage, providing an ideal protection against mold and
                       moisture damage. The hysteresis values can be adjusted, allowing
                       the device to be adapted to local conditions. One outside sensor
                       per system and one inside sensor per zone are required for
                       measuring temperature and humidity.
                       Data sheet no. 34120
                       TÜV certificate (downloadable from our website)

                       ADG = Article discount group



          108  |  Catalog 2025  |  Gas warning devices     To our online catalog: www.oprg.de/en/support/download-center
   103   104   105   106   107   108   109   110   111   112   113