Gas warning systems (analog technology)
                                                                      Type              Item no. ADG Euro  /  pc.

                       Gas warning device – for 1 gas sensor          GWA 01.6           100870  03   1,144.10
                       Gas warning device – for 2 gas sensors         GWA 02.6           100872  03  1,375.10
                       in compact design. For a continuous monitoring of the air for
                       flammable gases and toxic gas concentrations.
                       All sensors with signal output 4 – 20 mA can be connected.
                       Self and line monitoring, cold-start false alarm suppression,
                       2 programmable alarm switching points per measuring
                       point, alarm output: (contact load 250 V / 2.5 A)
                       1 floating change-over contact each for alarm 1 and alarm 2, 1
                       floating change-over contact, in switch mode / static for
                       warning lamp, alarm 1, 1 floating normally open contact for horn,
                       resettable, 1 floating change-over contact for device error, built-in
                       piezo buzzer with reset button, external reset can be connected
                       LED display for operation, alarm and error messages. Key switch for
                       alarm suppression in case of maintenance.
                       Housing dimensions:   200 x 140 x 60 mm (L x W x D)
                       Protection class:   IP 65
                       Data sheet no. 30101

                       Optionally also available with display         GWA xxx D         on request  on request