Sensors for air quality
                                                                            Type              Item no. ADG Euro  /  pc.

                             CO 2  - and temperature transducer
                             Measuring range CO 2 : 0 – 3,000 ppm; temperature 0 – 50 °C
                             (factory-made preset to 0 – 2,000 ppm) for regulation of the
                             demands of ventilation systems dependent on number of
                             people. The measuring principle is based on non-dispersive
                             infrared technology with automatic self-calibration. 5 year service
                             intervals. Output for CO 2  and temperature: 0 – 10 V or
                             4 – 20 mA each, programmable. If equipped with LCD display,
                             the concentration of CO 2  and the temperature are shown                                 SENSORS
                             alternately; serial communication interface.
                             Voltage supply:    24 V AC / DC ± 20 %
                             Permiss. amb. cond.:      0 – 50 °C, 0 – 95 % RH
                                                 (non-condensing)
                             Housing for vertical interior wall fastening.
                             Housing: 61 x 97 x 19 mm (L x W x D); white; IP 30

                             CO 2  and temperature transducer,              CO2-W-D-2.5       100092  01  603.60
                             with display
                             CO 2  and temperature transducer,              CO2-W-2.5         100083  01  543.00
                             without display
                             Data sheet no. 14101

                             CO 2  -transducer
                             Low cost specification, since there is no temperature output.
                             Indoor installation.
                             Measuring range CO 2 : 0 – 2,000 ppm
                             For regulation of the demands of ventilation
                             system dependent on number of people.
                             The measuring principle is based on non-dispersive
                             infrared technology with automatic self-calibration.
                             2 outputs:              1x 0 – 10 V and 1x 2 – 10 V / 4
                                                   – 20 mA (FAI: only 1x 0 – 10 V)
                             Power supply:         24 V AC / DC ± 20 %
                             Permiss. amb. cond.:      0 – 50 °C, 0 – 95 % RH
                                                   (non-condensing)
                             CO 2  transducer with display                  CO2-WD-LC         100089  01  523.20
                             CO 2  transducer without display               CO2-W-LC          100093  01  462.50
                             Data sheet no. 14106