Page 24 - Op_K_2025_absolute Links
P. 24

OPP-SENS®

          Temperature measuring transmitters
                                                                      Type              Item no. ADG Euro  /  pc.

                       OPP-SENS® Measuring transmitter for PT1000 cable sensor   M-...    see        see
                       Converts passive sensor signal PT1000 in 0 – 10 V                following   following
                       or 4 – 20 mA analog signals or communicates the                   page       page
                       temperature value via Modbus or BACnet. See catalog
                       page 29 for the accompanying PT1000 cable sensor
                       Display and control unit with autoadapt and capacitive
                       button (option). This enables the NFC function, allowing easy
                       sensor parameterization via a smartphone.
                       5-point calibration: linear interpolation of the output curve over
                       5 user-defined points.
                       10 offset points: linear shift of characteristic curve the output
                       signal via 10-level rotary switch.
                       Captive lid with 8-way positioning.

                       10 measurement ranges can be set using the rotary switch:
                       Note: scale only – please observe rated
                       media temperature for separate PT1000 cable sensor
                       -50 °C – 200 °C   -20 °C – 150 °C   -50 °C – 50 °C
                       -20 °C – 80 °C   -30 °C – 60 °C   0 °C – 40 °C
                       0 °C – 50 °C   0 °C – 100 °C*   0 °C – 150 °C
                       0 °C – 200 °C   *factory settings

                       Supply voltage:
                       2-wire           24 V DC
                       3-wire / Modbus / BACnet 24 V AC / DC
                       Output:
                       2-wire           4 – 20 mA
                       3-wire           0 – 10 V or 4 – 20 mA
                                        switchable or bus
                       Permiss. amb. cond.    -20 – 70 °C, 0 – 95 % RH
                                        (non-condensing)
                       Permiss.
                       media temperature:  depends on installed
                                        PT1000 cable sensor
                       Sensor element:    Sensor element: PT1000 sensor
                                        cable separately available.
                                        Connection via spring terminals
                       Housing:         IP 65 including seal,
                                        Plastic gray / yellow
                       Cable gland:     2 x M16 for analog versions
                                        2 x M16 + 1 x M12 for bus versions
                       Terminals:       Spring terminals 0.2 – 1.5 mm2

























          24  |  Catalog 2025  |  Sensors                 To our online catalog: www.oprg.de/en/support/download-center
   19   20   21   22   23   24   25   26   27   28   29