Page 28 - Op_K_2025_absolute Links
P. 28
OPP-SENS®
Air duct average temperature sensors
Type Item no. ADG Euro / pc.
OPP-SENS® Air duct temperature sensor (active), TA-Tx-I-xxx
average value for measuring of average temperatures in ventilation
ducts.
Fully active flexible sensor probe.
Measures average value over the entire length.
Captive lid with 8-way positioning.
Permiss. amb. cond.: -25 – 65 °C, 0 – 95 % RH
(non-condensing)
Permiss. media temp.: -30 – 105 °C
Nominal diameter: ø 6 mm
Installation: air duct mounting flange F-6
(included in scope of delivery)
Housing: IP 65 including seal,
Plastic gray / yellow
Cable gland: M16
Terminals: Spring terminals
4 measuring ranges (adjustable): -50 – 50 °C
*factory setting 0 – 50 °C
0 – 100 °C*
0 – 150 °C
Current transmitter (2-wire)
Supply: 24 V DC
Output: 4 – 20 mA
Voltage transmitter (3-wire)
Supply: 24 V AC / DC
Output: 0 – 10 V
Current transmitter (2-wire, 4 – 20 mA)
Sensor length 400 mm TA-TC-I-400 103069 22 192.00
Sensor length 3,000 mm TA-TC-I-3000 103061 22 217.80
Sensor length 6,000 mm TA-TC-I-6000 103063 22 256.40
Current transmitter (3-wire, 0 – 10 V)
Sensor length 400 mm TA-TV-I-400 103068 22 195.40
Sensor length 3,000 mm TA-TV-I-3000 103062 22 250.80
Sensor length 6,000 mm TA-TV-I-6000 103064 22 261.40
Data sheet no. 20906
Order code: TA-analog output-I-length
Example: TA-TC-I-6000: current transmitter (2-wire),
output 4 – 20 mA, sensor length 6,000 mm
Note: Further lengths available on request.
There are no displays, 5P calibration, no Safecabling and no
Bus transmitter available for this sensor.
Mounting clamp (1 Item) MK 101196 22 1.20
for average sensor
Note: We recommend 4 MK installation clamps per sensor of
3,000 mm length and 6 MK installation clamps per sensor of
6,000 mm length.
The number of installation clamps may vary depending on the
number of turns.
Data sheet no. 20906
28 | Catalog 2025 | Sensors To our online catalog: www.oprg.de/en/support/download-center