Page 90 - Op_K_2025_absolute Links
P. 90

Safety temperature limiter
                                                                      Type              Item no. ADG Euro  /  pc.

                       Electromechanical safety temperature limiter   STB-01             104217  02   71.40
                       For use in heat generators and other HVAC applications.
                       Intrinsically safe design. Rupture of the capillary tube causes the
                       contact to open. After a temperature-triggered shutdown the
                       sensor tube must be allowed to cool down by ca. 25 ± 5 K before
                       manual reset becomes possible.
                       There are various installation options: direct mounting on the
                       immersion sleeve, raised mounting, mounting on the pipe or in the
                       air duct.
                       If it is to be installed directly on the immersion sleeve, the safety
                       temperature limiter (STB) / temperature monitor (TW) must be
                       fastened on the immersion sleeve fitting. Immersion sleeves and
                       mounting hardware are not included in the scope of delivery.
                       Accessories are listed on pages 92 and 93. Immersion sleeves
                       TH should be selected from those listed under Accessories STB / TW
                       to ensure conformity to the requirements of EN 14597.

                       Protection type:    IP 66
                       Setting range:      90 – 110 °C
                       Length of capillary tube:   approx. 1 m
                       Electrical changeover contact:
                       Break contact       2,5 ... 10 A / 40 ... 250 V AC
                       Closing contact     0,5 A / 40 ... 250 V AC
                       Connection:         screw terminals
                       Cable grommet:      M20
                       Permiss. amb. cond.:     0 – 70 °C, 0 – 95 % RH
                                           (non-condensing)
                       Dimensions (W x H x D):   approx. 70 x 110 x 70 mm
                       Data sheet no. 20680













































          90  |  Catalog 2025  |  Sensors                 To our online catalog: www.oprg.de/en/support/download-center
   85   86   87   88   89   90   91   92   93   94   95