Page 86 - Op_K_2025_absolute Links
P. 86

Antifreeze controller
                                                                      Type              Item no. ADG Euro  /  pc.

                       2-phase antifreeze control, downstream - with display
                       for monitoring temperature of air heaters against freezing. Copper
                       capillary tube with precision switching mechanism and analog
                       output 0 –10 V for proportional opening of control valves. The
                       freeze protection monitor always responds to the coldest location
                       of the capillary tube (min. immersion depth: 250 mm). Setpoint
                       potentiometer, operating mode switch for ”Auto“, ”Test“, ”Manual“,
                       reset button, large display for operating mode and red LED for
                       freeze warning.
                       Supply voltage:        24 V AC +10 / -20 %; 50 / 60 Hz
                       Power consumption:     6.6 VA
                       Sensor / adjustable range:   0 – 15 °C / 1 – 10 °C
                       Default setting:       5 °C
                       Switching differential:   approx. 2 k
                       Relay output           (changeover contact)
                                              max.  6 A, 230 V AC; 6 A, 24 V DC
                                              min.  5 mA, 5 V AC / DC
                       Input / output signal:   0 – 10 V max 1 mA each
                       Rated device head temp.:   -15 – 55 °C
                       Protection type / class:   IP 42; I
                       Time constant:         calm air 90 sec
                                              moving air < 40 sec
                       Capillary tube:        Rated temperature max. 110 °C
                                                                 2
                       Electrical connections:    Spring clips max. 2 x 1.5 mm
                                              or 1 x 2.5 mm 2
                       Permiss.
                       ambient conditions:      -15 – 55 °C, 0 – 85 % RH
                                              (non-condensing)
                       Scope of delivery:       M16 cable gland, rubber
                                              grommet for feeding the capillary
                                              tubes through the duct and
                                              screw fasteners.

                       Capillary tube length 2 m, with 4 mounting clamps  OPP-FRO-S2     101297  02  275.70
                       Capillary tube length 6 m, with 6 mounting clamps  OPP-FRO-S6     101298  02  320.90
                       Data sheet no. 20672

                       Mounting clamps (replacement part 1 pc.)       MK                 101196  02   1.20
                       for antifreeze and average value sensors
                       Data sheet no. 20672




























          86  |  Catalog 2025  |  Sensors                 To our online catalog: www.oprg.de/en/support/download-center
   81   82   83   84   85   86   87   88   89   90   91