Differential air pressure transmitter
                                                                      Type              Item no. ADG Euro  /  pc.

                       Differential pressure transmitter              DDS-QR984xx
                       with automatic zero point adjustment
                       8 measuring ranges (Code QR) – adjustable
                       Complete unit (without fastening angles)
                       for vertical installation, consisting of:
                       Differential pressure monitor and clima-set straight type 6555.

                       Output signal:      switchable root extracting / linear
                       Output:               0 – 10 V or 4 – 20 mA adjustable
                                           (3-wire) with additional npn open
                                           collector switching output
                       Dimensions:           ø 85 x 58 mm (L x W),
                       protection class:    IP 54
                       Voltage supply:     18 – 30 V AC, 16 – 32 V DC (3-wire)
                       Uncertainty (total error disregarding long-time and
                       temperature influences):    ±1% of full scale, min. ±1 Pa
                       Permiss. amb. cond.:    -10 – 50 °C, 0 – 95 % RH
                       (non-condensing)
                       Data sheet no. 13252
                       without display                                DDS-QR984.5.5.3.K.0  103597  12  241.40
                       with display                                   DDS-QR984.5.5.3.K.1  103598  12  284.40

          Type             Switch   DDS-QR984.5.5.3.K.1
                           position  Pressure measuring   Temperature
                                    range            error
          DDS-QR984.5.5.3.K.1  1    ±100 Pa          ≤ ± 4 % v. EW
                           2        0 – 100 Pa       ≤ ± 5 % v. EW
          Overpressure safety:   3  0 – 200 Pa       ≤ ± 4 % v. EW
          85 kPa           4        0 – 500 Pa       ≤ ± 2,5 % v. EW
                           5        0 – 1,000 Pa     ≤ ± 1,5 % v. EW
          Cracking pressure:    6   0 – 1,500 Pa     ≤ ± 1,5 % v. EW
          135 kPa          7        0 – 2,000 Pa     ≤ ± 1 % v. EW
                           8        0 – 2,500 Pa*    ≤ ± 1 % v. EW
                           LO       Test 0 V / 4 mA  -
                           HI       Test 10 V / 20 mA  -
          DDS-QR984.….K.0  without display, technical information as above
                       * = Factory setting
                       without display                                DDS-QR984.5.4.3.K.0  103097  12  241.40
                       with display                                   DDS-QR984.5.4.3.K.1  103098  12  284.40

          Type             Switch   DDS-QR984.5.4.3.K.1
                           position  Pressure measuring   Temperature
                                    range            error
          DDS-QR984.5.4.3.K.1  1    0 – 100 Pa       ≤ ± 4 % v. EW
                           2        0 – 250 Pa       ≤ ± 3,5 % v. EW
          Overpressure safety:   3  0 – 500 Pa       ≤ ± 2 % v. EW
          75 kPa           4        0 – 1,000 Pa*    ≤ ± 1 % v. EW
                           5        ± 50 Pa          ≤ ± 4 % v. EW
          Cracking pressure:    6   ± 100 Pa         ≤ ± 3 % v. EW
          125 kPa          7        ± 250 Pa         ≤ ± 2 % v. EW
                           8        ± 500 Pa         ≤ ± 1 % v. EW
                           LO       Test 0 V / 4 mA  -
                           HI       Test 10 V / 20 mA  -
          DDS-QR984.….K.0  without display, technical information as above
                       * = Factory setting




          62  |  Catalog 2025  |  Sensors                 To our online catalog: www.oprg.de/en/support/download-center