Page 60 - Op_K_2025_absolute Links
P. 60

Differential air pressure transmitter
                                                                      Type              Item no. ADG Euro  /  pc.

                       Differential pressure transmitter              DDS-MR984xx
                       with manual zero point adjustment
                       Complete unit (without fastening angles)
                       for vertical installation, consisting of: Differential pressure monitor
                       and clima-set straight type 6555.
                       2 measuring ranges,
                       Output signal:      switchable root extracting / linear
                       Output:               0 – 10 V or 4 – 20 mA adjustable
                                           (3-wire) or 4 – 20 mA linear (2-wire)
                                           with additional npn open collector
                                           switching output
                       Dimensions:         ø 85 x 58 mm (L x W),
                       protection class:    IP 54
                       Voltage supply:       18 – 30 V AC, 16 – 32 V DC (3-wire) or
                                           18 – 30 V DC (2-wire)
                       Uncertainty (total error disregarding long-time and
                       temperature influences):    ±1% of full scale, min. ±1 Pa
                       Permiss. amb. cond.:     -20 – 70 °C, 0 – 95 % RH
                                           (non-condensing)
                       Data sheet no. 13251
                       without LED display                            DDS-MR984.5.….3.K.0 s. table  12 on requ.
                       with LED display                               DDS-MR984.5.….3.K.1  on   12 on requ.
                                                                      … = Code for pressure  request
                                                                      range
                                                                      see sample table
                                                                      below

                        Type                    Item no.  Measuring   Measuring    Overpress.  Cracking
                        (Pressure range)                  range 1     range 2      safety      pressure
                        DDS-MR984.5.X.3.K.0     100255    ± 50 Pa     -            60 kPa      100 kPa
                        DDS-MR984.5.W.3.K.0     103434    ± 100 Pa    -            60 kPa      100 kPa
                        DDS-MR984.5.M.3.K.0     103209    ± 150 Pa    -            60 kPa      100 kPa
                        DDS-MR984.5.N.3.K.0     100265    ± 250 Pa    -            60 kPa      100 kPa
                        DDS-MR984.5.S.3.K.0     100268    ± 1,000 Pa  -            75 kPa      125 kPa
                        DDS-MR984.5.2.3.K.0     100249    0 – 100 Pa  0 – 250 Pa   60 kPa      100 kPa
                        DDS-MR984.5.3.3.K.0     100250    0 – 250 Pa  0 – 500 Pa   75 kPa      125 kPa
                        DDS-MR984.5.4.3.K.0     100251    0 – 500 Pa  0 – 1,000 Pa  75 kPa     125 kPa
                        DDS-MR984.5.5.3.K.0     100254    0 – 1 kPa   0 – 2,5 kPa  85 kPa      135 kPa
                        DDS-MR984.5.7.3.K.0     100256    0 – 5 kPa   0 – 10 kPa   135 kPa     275 kPa
                        DDS-MR984.5.9.3.K.0     100258    0 – 25 kPa  0 – 50 kPa   200 kPa     400 kPa
                        DDS-MR984.5.B.3.K.0     100247    0 – 100 kPa  0 – 250 kPa  400 kPa    800 kPa
                        DDS-MR984.5.….3.2.0    on request  2-wire 4 – 20 mA, no switching output, no display possible
                       All 3-wire versions also available with display.

                       Type designation

                               Type                        M   2 or 1 measuring range (depending on type), manual zero adjustment
                                     Cable screw joint M16  A   2 measuring ranges, automatic zero adjustment
                                      Measuring range,
                                      see pressure range table  Q   8 measuring ranges, automatic zero adjustment
                                       Measuring unit Pa
                                        K=  Standard features: Output signal 0 – 10 V or 4 – 20 mA.
                                          Output switchable lin. / rad. With npn-switching output.
                                        2 = 2-wire 4 – 20 mA. Without switching output. Without display. lin. / rad. switchable.
                                          Display          0   without display
                                                           1   with LED display
                        DDS-MR984.5._.3.K .1
                        DDS- AR984.5._.3.K .1
                        DDS- QR984.5.4.3.K .1



          60  |  Catalog 2025  |  Sensors                 To our online catalog: www.oprg.de/en/support/download-center
   55   56   57   58   59   60   61   62   63   64   65