Page 119 - Op_K_2025_absolute Links
P. 119

GAS
                                                                                                           GAS
               Gas measuring sensor selection table



               Type of gas /     OEL-  Measuring   rel. gas density /  Data sheet  Type       Item no. ADG Euro / pc.
               Formula       value*   range     install. height  no.

               Oxygen
               O 2                    0 – 25 Vol %  1,0 / 1,5 – 1,8 m  GMF 2.E.O2.54          100599  03  912.90
               O 2                    0 – 25 Vol %  1,0 / 1,5 – 1,8 m  GMF 2.Z.O2.54          100648  03  2,463.30
               O 2                    0 – 25 Vol %  1,0 / 1,5 – 1,8 m  38112  GMF 4.Z.O2.54.MOD  104181  03  1,316.30
               O 2                    0 – 95 Vol %  1,0 / 1,5 – 1,8 m  38112  GMF 4.Z.O2.55.MOD  104491  03  1,316.30

               Sulfur dioxide
               SO 2          2,0 ppm  0 – 20 ppm  2,21 / floor  37401  GMF 2.E.SO2.03         100604  03  861.80
               Hydrogen sulfide
               H 2 S         10 ppm   0 – 100 ppm  1,19 / floor  37401  GMF 2.E.H2S.07        100592  03 1,327.10

               Nitrogen dioxide
               NO 2          5 ppm    0 – 20 ppm  1,59 / floor  37111  GMF 4.E.NO2.03         100769  03  573.80
               NO 2          5 ppm    0 – 20 ppm  1,59 / floor  38101  GMF 4.E.NO2.03.MOD     100771  03  485.80
               NO 2          5 ppm    0 – 20 ppm  1,59 / floor  38107  GMF 5.E.NO2.03.MOD     100778  03  475.70
               Nitrogen monoxid
               NO            25 ppm   0 – 100 ppm  1,04 / floor  37401  GMF 2.E.NO.07         100598  03 1,606.10

               Styrene
               C 8 H 8       20 ppm   0 – 100 % UEG 3,59 / floor  37301  GMF 2.H.C8H8.30      100618  03  869.40
               Toluene
               C 7 H 8       50 ppm   0 – 100 % UEG 3,18 / floor  37301  GMF 2.H.C7H8.30      100617  03  912.90

               Tetrahydrofuran
               CH 4 H 8 O    50 ppm   0 – 100 % UEG 2,49 / floor  37301  GMF 2.H.CH4H8O.30    100607  03  820.80      GAS WARNING DEVICES

               Hydrogen
               H 2                    0 – 4 Vol %  0,5 / ceiling  37401  GMF 2.E.H2.30        100593  03 1,327.10
               H 2                    0 – 100 % UEG 0,5 / ceiling  37301  GMF 2.H.H2.30       100621  03  912.90
               H 2                    0 – 100 % UEG 0,5 / ceiling  38113  GMF 4.H.H2.30.MOD   104610  03  546.30
               H 2                    0 – 100 % UEG 0,5 / ceiling  37201  GMF 2.P.H2.30       100646  03  912.90
               Double gas measuring sensor DUO-MOD
               consisting of
               Carbon monoxide        0 – 300 ppm  0,97 / 1,5 – 1,8 m 38104  GMF.DUO.E.CO.08.MOD  100839  03  755.90
               LPG / Pellistor        0 – 100 % UEG 1,56 / floor  38104  GMF.DUO.P.C3H8.30.MOD
               Housing type 4

               Combined sensor CO / NO2-MOD
               For simultaneous measurement of CO and NO2 in a single unit.
               Mounting height for target gas CO. Observe the local rules/regulations!

               Carbon monoxide        0 – 300 ppm  0,97/1,5 – 1,8m 38108  GMF 5.E.CO+NO2.08+03.MOD  100775  03  759.90
               Nitrogen dioxide       0 – 20 ppm







               * The occupational limit values serve as non-binding guidelines. Please observe the applicable local regulations.




               To our online catalog: www.oprg.de/en/support/download-center    Catalog 2025  |  Gas warning devices  |  119
   114   115   116   117   118   119   120   121   122   123   124