Page 68 - Op_K_2025_absolute Links
P. 68

OPP-SENS®

          Volume flow temperature transmitter
                                                                      Type              Item no. ADG Euro  /  pc.

                       OPP-SENS® Volume flow temperature transmitter  VT…                 See        See
                       for measuring of volume air flow in ducts, with adjustable       following   following
                       mounting for adjusting the depth of immersion.                    page       page
                       Via the optional display, the transmitter can be configured to show
                       either flow volume in m³/h or flow velocity in m/s. The size of the
                       duct and a correction factor can also be set via the display. The
                       microprocessor technology guarantees a constant linear output,
                       even at low air speeds.
                       Illuminated display & control unit with
                       autoadapt and capacitive buttons. The duration of lighting,
                       contrast, display (temperature, flow or alternating) and
                       temperature unit can be set via the menu.
                       5-point calibration: linear interpolation of the output
                       curve over 5 user-defined points.
                       10 offset points: linear shift of characteristic curve
                       the output signal via 10-level rotary switch.
                       Captive lid with 8-way positioning.

                       Volume flow measurement range:
                       0 – 9,999 m³ / h, use correction factors for parametrization

                       10 measurement ranges can be set using the rotary switch:
                       Volume flow mode:
                       0 – 250 m³ / h   0 – 500 m³ / h   0 – 1,000 m³ / h   0 – 2,000 m³ / h
                       0 – 3,000 m³ / h  0 – 4,000 m³ / h  0 – 5,000 m³ / h*  0 – 6,000 m³ / h
                       0 – 7,500 m³ / h  0 – 9,999 m³ / h  *factory setting

                       Air flow mode:
                       0 – 2 m / s   0 – 2,5 m / s   0 – 4 m / s   0 – 5 m / s
                       0 – 6 m / s   0 – 8 m / s   0 – 10 m / s   0 – 12 m / s
                       0 – 15 m / s   0 – 20 m / s
                       Temperature
                       measurement range:   Factory setting 0 – 50 °C,
                       optional display between -50 and 100 °C can be set
                       Permiss. amb. cond.:      -20 – 70 °C, 0 – 95 % RH
                                           (non-condensing)
                       Permiss.
                       media temperature:   -20 – 100 °C
                       Supply voltage:     24 V AC / DC
                       Output volume- / air flow:    0 – 10 V or 4 – 20 mA
                                           switchable or bus
                       Output temperature:      0 – 10 V or 4 – 20 mA
                                           switchable or bus
                       Nominal size:       ø 10 mm stainless steel sleeve
                       Duct cross-section max:   600 x 600 mm or ø 600 mm
                       Mounting:           Air duct flange F-10 (included)
                       Housing:            IP 65 including seal, Plastic gray / yellow
                       Cable gland:        M16
                       Teminals:           Spring terminals 0.2 – 1.5 mm2















          68  |  Catalog 2025  |  Sensors                 To our online catalog: www.oprg.de/en/support/download-center