Senso
Volume flow indicator & transmitter
Type Item no. ADG Euro / pc.
Low-pressure flow indicator-transmitter-monitor Senso VP see our
Highly accurate – especially for volume flow current
measurements with pitot tubes (e. g. Prandtl). price list
Round built-in type unit with large LCD display.
k value and r (Rho) programmable.
Units of measure: m³ / h or l / sec or ft³ / min
Adjustable threshold with red LED indication in case of undershoot.
Working range: 0 – 99,990 m³/h
Error margin: ± 1 Pa (Tu 10 °C – 30 °C)
± 2 Pa (Tu < 10 °C or > 30°C)
analog output ≤ 1% of
measuring range
Measuring range: 0 – 250 Pa
Installation
dimensions: 114 x 48 mm (ø x H)
2 connection fittings: ø 6 mm flush with the rear side
Supply voltage: 24 V AC / DC
Output 1: 0(2) – 10 V ≙ 0 – 99,990 m³/h
Output 2: 0(4) – 20 mA ≙ 0 – 99,990 m³/h
Output 3: relay with floating changeover
contact
Protection class: IP 54, with additional O-Ring IP 64
(see accessories)
Permiss.
amb. cond. -10 – 40 °C, 0 – 75 % RH
(non-condensing)
Senso accessories on page 58
Note: Please order together with the desired clima-set
(straight or right-angle) for the connection (see page 58).
Snap-fit cover for built-in type unit,
including Senso-ZP-type mounting set
square design VP250-00-SET 102835 13
round design VP250-01-SET 102836 13
Surface-mounted housing configuration
Technical specifications as above, but with protection class IP 65 VP250-AP 104163 13
and differing dimensions; connection fittings / electrical connection
pointing down; without assembly kit.
Data sheet no. 13159